Heating Circuit System for Thermostat


This is a circuit for heating in the thermostat that is intended to control a heating system or central heating plan, keeping constant indoor temperature in spite of wide range changes in the outdoor one. Two sensors are needed: one placed outdoors, in order to sense the external temperature; the other placed on the water-pipe returning from heating system circuit, short before its input to the boiler. The output from the Relay contact must be connected to the boilers start-stop control input. This is the figure of the circuit;


When Q1 Base to ground voltage is less than half voltage supply (set by R7 & R9), a voltage is generated across R8 and the driver transistors Q2 & Q3 switch-on the Relay. When Q1 Base to ground voltage is more than half voltage supply, caused when one of the n.t.c. Thermistors lowers its value due to an increase in temperature, no voltage appears across R8 and the Relay is off. C3 allows a clean switching of the Relay. P1 acts as main temperature control.

Part;
P1 1K Linear Potentiometer
R1 10R 1/4W Resistor
R2 1K 1/4W Resistor
R3 3K3 @ 20°C n.t.c. Thermistor (see Notes)
R4 2K2 @ 20°C n.t.c. Thermistor (see Notes)
R5 10K 1/2W Trimmer Cermet
R6 3K3 1/4W Resistor
R7,R9 4K7 1/4W Resistors
R8 470K 1/4W Resistor
R10 10K 1/4W Resistor
C1,C2 470µF 25V Electrolytic Capacitors
C3 1µF 63V Electrolytic Capacitor
D1,D2,D4 1N4002 100V 1A Diodes
D3 LED Red 3 or 5mm.
Q1 BC557 45V 100mA PNP Transistor
Q2 BC547 45V 100mA NPN Transistor
Q3 BC337 45V 800mA NPN Transistor
RL1 Relay with SPDT 2A @ 220V switch
Coil Voltage 12V. Coil resistance 200-300 Ohm
J1 Two ways output socket
SW1 SPST Mains Switch
T1 220V Primary, 12 + 12V Secondary 3VA Mains transformer
PL1 Male Mains plug & cable